In order to promote public education and public safety, equal justice for all, a better informed citizenry, the rule of law, world trade and world peace, this legal document is hereby made available on a noncommercial basis, as it is the right of all humans to know and speak the laws that govern them.
IS 13039: 1991
(Reaffirmed 2000)
UDC 614·843·1·004·5: 006·76
© BIS 1991
BUREAU OF INDIAN STANDARDS
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002
March 1991
Price Group 2
iFire Fighting Sectional Committee, CED 22
This Indian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the Fire Fighting Sectional Committee had been approved by the Civil Engineering Division Council.
One of the methods for extinguishing fire in towns, cities and industrial buildings is by providing external hydrant systems. Fire hydrant systems consist of suitable capacity reservoirs, arrangements to impart pressure to the water, means to convey the water to various locations and suitable water outlets at the required locations. In order that such system could function efficiently, it will be necessary to give guidance for the provision, installation, inspection and maintenance of this system. This standard covers minimum requirements for such system. The provisions for this system were earlier covered in IS 9668: 1980 ‘Code of practice for provision and maintenance of water supplies for fire fighting’ and during the revision of IS 9668: 1980, the requirements of that standard have been limited to the water supply and the external hydrant system has been covered separately in this standard incorporating modifications based on the experience gained in the use of the system. The provision of internal hydrant is covered in IS 3844: 1989. ‘Code of practice for installation and maintenance of internal hydrants and hose reel on premises (first revision)’.
iiIndian Standard
EXTERNAL HYDRANT SYSTEMS—
PROVISION AND MAINTENANCE—
CODE OF PRACTICE
This standard covers provisions of installation, inspection and maintenance of external hydrant systems.
The Indian Standards listed in Annex A are necessary adjuncts to this standard.
The water reservoirs to feed the fire hydrant system should be provided underground, at ground level or at higher level. The capacity and the details of such reservoirs are given in IS 9668: 1991.
The static fire fighting pumps shall conform to the requirements given in IS 12469: 1988. The capacity of pumps should be worked out based on requirements of output and pressure for the system. Provision shall be made for standby pumps fed from different source of power at the rate of 50 percent of aggregate number of pumps, subject to minimum of one and maximum of two. Where pumps are of different capacities, standby pump should be of highest capacity.
The mains should be of cast iron pipes conforming to IS 1536: 1976, IS 8329: 1977, IS 1537: 1976 and IS 7181: 1986 or mild steel conforming to IS 1239 (Part I): 1979 or IS 3589: 1981. The fittings of cast iron pipes should conform to IS 1538 (Parts 1 to 23): 1976 and of mild steel pipes conform to IS 1239 (Part 2): 1982.
Underground mains should be laid not less than 1 m below ground level. Where soil conditions are unsatisfactory, masonry or equal supports should be provided at regular intervals.
Above ground mains should be adequately supported at regular intervals not exceeding 3.5 m. When located near buildings, the main should be at least 2 m away from the face of the building.
The fire hydrant mains should always be laid in rings or crosslinked rings, that is, all the mains should be interconnected. The size of main should depend on the output and pressure requirements and the total number of hydrants to be installed on a single system. However, the minimum size of mains should be not less than. 150 mm.
Adequate number of sluice valves distributed according to the general layout of the installation should be provided for the purpose of isolating any portion of the installation for purposes of repairs, etc.
All sluice valves should conform to IS 780: 1984 and enclosed in properly constructed surface boxes so as to allow for broken joints being easily re-made. Valve wheels should have an arrow head engraved or cast thereon showing direction for turning ‘Open’ and ‘close’.
The mains should not be laid under buildings, large open storages, railway lines and roads carrying very heavy traffic as far as possible. Where, however, it is inescapable to lay mains under the above condition, they should be laid in masonry trenches with removable covers and sluice valves should be provided at the points of entry and exit.
The mains should be laid according to the provision given in IS 5822: 1986 and IS 10221: 1982, asapplicable.
The ground hydrant system should normally not be extended to feed riser main in storeyed buildings. Only in special circumstances building not exceeding 15 m. in height, an extension may be used, provided sufficient output and pressure-can be ensured from the system. In such cases, since ring mains may not be possible, terminal main of not less than 100 mm diameter to feed up to three hydrants and 150 mm dia to feed up to five hydrants may be used.
Fire fighting mains should not be utilized for any other purpose such as process use for industrial premises.
Fire hydrants, namely, stand post type, conforming to IS 908: 1975 and underground type conforming to IS 909: 1975 should be provided. For use in industrial establishment, only stand post type hydrants should be provided.
For cities and towns, stand post type hydrants should be provided preferably but where these
1are likely to cause obstruction to traffic or are liable to be misused by public, underground type may be provided.
Hydrant outlet and valve for the underground type hydrant and valves for the stand post type hydrant should be located as near the ground level as possible. The top of the outlet or spindle of the valve should be at a depth not exceeding 0.3 m.
Ordinary manhole covers of cast iron or reinforced concrete should not be used to cover underground hydrants or the valves of the stand post type hydrants. They should be covered only by hinge cast iron covers as specified in IS 3950: 1979 with letters ‘FH’ embossed on them.
Apart from painting the fire hydrants and their covers in distinctive colours, all fire hydrants should have suitable indicating plates fixed to the nearest wall or suitable post erected for the purpose to facilitate easy location. The indicating plates can be made of vitreous enamelled mild steel, cast iron, aluminium alloy or plastic. The plates should be yellow in colour with letter ‘H’ in black, preferably with fluorescent colour paints. Where possible, size of the mains and the distance of the hydrant from the plate should be marked on the plate.
Normally in towns/cities, the hydrants should be provided at intervals of 100 m but this distance may be suitably increased or decreased depending on the risk in the area desired to be protected.
In case of industries of high hazard category (Gr G-3, H and J), the hydrants should be installed at every 30 m apart along building line and the hydrant outlet should be single or double hydrant with provision of landing valves. For moderate hazard (Gr G-2) where the single hydrant is use, it should be installed at every 45 m apart. In case of any portion which has multiple hazards, the relevant portion should be covered according to the provision given for higher hazard. Further the pressure available at hydraulically most remote hydrant should not be less than 3.5 kgf/cm3 for light (Group A to F) and moderate hazard. In case of high hazard (Group G-3, H and J), the hydrant system (Group G-2) should be so designed that when half the aggregate pumping capacity is being discharged at the hydraulically most remote point and other half in the most vulnerable area enroute a minimum pressure of 5.25 kg/cm2 is available at the remote point. For group classification IS 1641: 1988 should be referred to.
The hydrants should be located according to the attendant fire hazard so as to facilitate the most effective service. They need not necessarily be equidistant from each other. In industries where they are to cover specific buildings, advantage should be taken of convenient doors or windows or both, to place hydrants so that only a minimum length of hose is required to reach the opening through which fires may be attacked The location of hydrant landing valves on floors above the ground floor or a processing unit should be close to the staircase landings.
Hydrants should be located at a distance of not less than 2 m from the face of the buildings. This distance may suitably be increased up to maximum 15 m where hydrants are installed to protect hazardous storages or processes so that the haydrants remain approachable and workable even in the case of a serious fire.
All hydrants should be readily accessible to the fire appliances and for fire fighting operations.
Hydrants located in situations where they are likely to be damaged by vehicular traffic should be suitably protected on all sides against possible damage.
In cold climates where frost is likely to be experienced, the hydrants should be fitted with suitable means for draining off the water trapped in the body of the hydrant between the valve and the outlet.
No portion of a protected building should be more than 45 m from an external hydrant, and where this requirement cannot be met, internal hydrants/landing valves should be provided (see IS 3844: 1966).
Hydrant accessories, such as, hydrant stand pipes, hydrant key and bar suction collecting heads, delivery hoses, branch pipes and nozzles, etc, should be provided in sufficient quantities for quick operation of the hydrants.
In case of industries having their own fire brigades, the hydrant accessories should be provided centrally on each of the fire appliance and at the fire station. However, in the case of industries which do not have their own brigade or where it is intended that the train ed. worker s will engage in interim fire fighting, the appropriate essential accessories should be provided near each hydrant point in hydrant boxes of adequate size. In such cases, delivery hoses should be provided at the scale of two, 63 mm hoses generally conforming to type A of IS 636: 1988, duly bound with instantaneous couplings in 15 m lengths and one branch pipe duly fitted with a nozzle (preferably universal branch conforming to IS 2871:1983). The key and other accessories should be provided according to the peculiar needs of each system.
2After installation the system should be capable of withstanding pressure equal to 150 percent of the maximum working pressure for 2 h.
Each hydrant provided in the area should be inspected as often as possible. The periodicity for such inspections should be determined and laid down depending on the local conditions. However, for cities and towns, such inspections for each hydrant should be carried out at intervals not exceeding one month and for industrial establishment once every week. The record of all such inspections should be maintained and remedial action for any defects observed should be immediately taken on priority basis.
The following action should be taken during the monthly/weekly inspections:
Apart from the monthly/weekly inspections, the performance of the hydrants should be thoroughly checked during the fire fighting operations and regular drills and practices. The practices should be so arranged that the maximum number of hydrants in different areas are operated in rotation.
Testing of pressure and output in different areas covered by the hydrant system should be carried, at least every quarter. Hydrant mains should be tested with the pump delivering at its maximum pressure with all the hydrants outlet closed and thereafter, with at least three adjacent hydrants opened to see that the hydrant yield the minimum output of 1 125 litres per minute at a minimum pressure of 5.25 kgf/cm2 or higher, if needed. During such tests, apart from the senior officers of the fire authority, water department engineers should also be associated. The results of such tests should be recorded and remedial action taken where pressure and output fall short of the stipulated requirements.
Proper handling and working of the hydrants can go a long way in their better maintenance and satisfactory performance over long period. The following simple rules should be followed whenever hydrants are operated:
(Clause 2)
| IS No. | Title |
|---|---|
| 636: 1988 | Non-percolating flexible fire fighting delivery hose (third revision) |
| 780: 1984 | Sluice valves for water works purposes (50 to 300 mm size) (sixth revision) |
| 908: 1975 | Fire hydrant, stand post type (second revision) |
| 909: 1975 | Underground fire hydrant, sluice valve type (second revision) |
| 1239 (Part 1): 1979 |
Mild steel tubes, tubulars and other wrought steel fittings: Part 1 Mild steel tubes (fourth revision) |
| 1239 (Part 2): 1982 |
Mild steel tubes, tubulars and other wrought steel pipe fittings: Part 2 Mild steel tubulars and other wrought steel pipe fittings (third revision) |
| 1536: 1976 | Centrifugally cast (spun) iron pressure pipes for water, gas and sewage (second revision) |
| 1537: 1976 | Vertically cast iron pressure pipes for water, gas and sewage (first revision) |
| 1538 (Parts 1 to 23): 1976 1641: 1988 |
Cast iron fittings for pressure pipes for water, gas and sewage Code of practice for fire safety of buildings (general): General principles of fire grading and classification (first revision) |
| 2871: 1983 | Branch pipe, universal for fire fighting purposes (first revision) |
| 3589: 1981 | Electrically welded steel pipes for water, gas and sewage 150 to 2000 mm nominal size) (first revision) |
| 3844: 1966 | Code of practice for installation and maintenance of internal hydrants and hose-reel on premises (first revision) |
| 3950: 1979 | Surface boxes for sluice valves (first revision) |
| 5822: 1986 | Code of practice for laying of welded steel pipes for water supply (first revision) |
| 7181: 1986 | Horizontally cast iron double flanged pipes for water, gas and sewage (first revision) |
| 8329: 1977 | Centrifugally cast (spun) ductile iron pressure pipes for water, gas and sewage (first revision) |
| 9668: 1991 | Code of practice for provision and maintenance of water supplies for fire fighting (first revision) |
| 10221: 1982 | Code of practice for coating and wrapping of underground mild steel pipelines |
| 12469: 1988 | Pumps for fire fighting applications |
Standard Mark The use of the Standard Mark is governed by the provisions of the Bureau of Indian Standards Act, 1986 and the Rules and Regulations made thereunder. The Standard Mark on products covered by an Indian Standard conveys the assurance that they have been produced to comply with the requirements of that standard under a well defined system of inspection, testing and quality control which is devised and supervised by BIS and operated by the producer. Standard marked products are also continuously checked by BIS for conformity to that standard as a further safeguard. Details of conditions under which a licence for the use of the Standard Mark may be granted to manufacturers or producers may be obtained from the Bureau of Indian Standards. |
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote harmonious development of the activities of standardization, marking and quality certification of goods and attending to connected matters in the country.
BIS has the copyright of all its publications. No pan of these publications may be reproduced in any form without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Indian Standards are reviewed periodically and revised, when necessary and amendments, if any, are issued from time to time. Users of Indian Standards should ascertain that they are in possession of the latest amendments or edition. Comments on this Indian* Standard may be sent to BIS giving the following reference:
Doc: No. CED 22 (4794)
| Amend No. | Date of Issue | Text Affected |
|---|---|---|
BUREAU OF INDIAN STANDARDS
| Headquarters: | |
| Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telephones: 331 01 31, 331 13 75 | Telegrams: Manaksanstha (Common to all Offices) |
| Regional Offices: | Telephone |
| Central: Manak Bhavan, 9 Bahadur Shah Zafar Marg NEW DELHI 110002 | 331 01 31 331 13 75 |
| Eastern: 1/14 C. I. T. Scheme VII M, V. I. P. Road, Maniktola CALCUTTA 700054 | 87 86 62 |
| Northern: SCO 445-446, Sector 35-C, CHANDIGARH 160036 | 53 38 43 |
| Southern: C. I. T. Campus, IV Cross Road, MADRAS 600113 | 41 29 16 |
| Western: Manakalaya, E9 MIDC, Marol, Andheri (East) BOMBAY 400093 | 6 32 92 95 |
| Branches: AHMADABAD. BANGALORE. BHOPAL. BHUBANESWAR. COIMBATORE. FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR. PATNA. THIRUVANATHAPURAM. | |